Infrastructure physical layer connection in data centre, LAN cabling backbone systems, backbone connectivity in building and campus.
Comply with TIA/EIA 604-5, IEC 61754 series,Telcodia GR-1435-CORE Issue 2,Telcodia GR-326-CORE Issue 4 standards.
Fire resistance comply with low smoking (IEC 61304), halogen free (IEC 60754-1), flame retardant (IEC 60332- 3C), and corrosion proof (IEC 60754-2)
Fibre Count |
Fan-out Length (cm) |
Pulling Hook |
Bending Radius(mm) | Temperature (℃) |
Package |
||||
---|---|---|---|---|---|---|---|---|---|
Tenson(N) | Impact(N/cm) |
Static |
Dynamic |
Operation |
Installation |
Storage |
|||
12 |
60 - 100 |
400 |
100 |
400 |
20D |
-20 to +60 |
-5 to +50 |
-25 to +75 |
PE bag for
|
24 |
60 - 100 |
600 |
100 |
450 |
20D |
-20 to +60 |
-5 to +50 |
-25 to +75 |
|
48 |
60 - 100 |
600 |
100 |
450 |
20D |
-20 to +60 |
-5 to +50 |
-25 to +75 |
|
72 |
60 - 100 |
600 |
100 |
450 |
20D |
-20 to +60 |
-5 to +50 |
-25 to +75 |
|
96 |
60 - 100 |
600 |
100 |
450 |
20D |
-20 to +60 |
-5 to +50 |
-25 to +75 |
|
144 |
60 - 100 |
600 |
100 |
450 |
20D |
-20 to +60 |
-5 to +50 |
-25 to +75 |
Connector Type |
IL(dB) |
500times Durability ΔIL(dB) |
Temperature Cycling ΔIL(dB) |
---|---|---|---|
MPO/MTP MM Elite |
≤0.35 |
≤0.20 |
≤0.20 |
MPO/MTP SM Elite |
≤0.35 |
≤0.20 |
≤0.20 |
MPO/MTP MM standard |
≤0.70 |
≤0.20 |
≤0.20 |
MPO/MTP SM standard |
≤0.70 |
≤0.20 |
≤0.20 |
LC MM connector |
≤0.30 |
≤0.20 |
≤0.20 |
LC SM connector |
≤0.30 |
≤0.20 |
≤0.20 |
Fibre Type |
Core/Cladding Dia.(µm) |
Bandwidth(MHz·km) |
Wavelength(nm) |
Max. Attenuation(dB/km) |
---|---|---|---|---|
G652D |
9/125 |
NA |
1310/1550 |
0.36/0.22 |
G657A2 |
9/125 |
NA |
1310/1550 |
0.36/0.22 |
OM1 |
62.5/125 |
200 |
850/1300 |
3.0/1.0 |
OM2 |
50/125 |
500 |
850/1300 |
3.0/1.0 |
OM3 |
50/125 |
2000 |
850/1300 |
3.0/1.0 |
OM4 |
50/125 |
4700 |
850/1300 |
3.0/1.0 |