Item |
Type |
Dimensions |
Capacity (Core) |
Operating Environment | Remarks |
---|---|---|---|---|---|
H × W × D (mm) | |||||
19" rack-mounted terminal box (1U) |
GZR-12SC |
1U × 482 × 220 |
12 |
Standard 19" rack/cabinet |
Configured with two 6-core SC panels and one blank panel |
GZR-12FC |
12 |
Configured with two 6-core FC panels and one blank panel |
|||
GZR-12ST |
12 |
Configured with two 6-core ST panels and one blank panel |
|||
GZR-24SC |
24 |
Configured with three 8-core SC panels |
|||
GZR-24FC |
24 |
Configured with three 8-core FC panels |
|||
GZR-24ST |
24 |
Configured with three 8-core ST panels |
|||
GZR-24DLC |
24 |
Configured with two 12-core duplex LC panels |
|||
GZR-48DLC |
48 |
Configured with three 16-core duplex LC panels |
|||
19" rack-mounted terminal box (2U) |
GZR-48SC |
2U × 482 × 220 |
48 |
Configured with six 8-core SC panels |
|
GZR-48FC |
48 |
Configured with six 8-core FC panels |
|||
GZR-48ST |
48 |
Configured with six 8-core ST panels |
|||
GZR-96DLC |
96 |
Configured with six 16-core duplex LC panels |
Product Series |
GZR series |
---|---|
Operating Temperature |
-40°C to +60°C |
Ambient Humidity |
≤ 95% (+40°C) |
Atmospheric Pressure |
70 kPa to 106 kPa |
Nominal Operating Wavelength |
850 nm, 1310 nm, 1550 nm |
Insulation Resistance |
Insulation resistance between ground device and cabinet > 1,000 MΩ/500 V (DC) |
Withstand Voltage (V) |
Withstand voltage between the ground part and cabinet > 3,000 V (DC)/5 s, no puncturing or arcing |
Insertion Loss (dB) |
≤ 0.2 dB |
Return Loss (dB) |
PC ≥ 45dB, UPC ≥ 50dB, APC ≥ 60dB |
Standards Compliance |
Other specifications compliant with the requirements of YD/T 778-2011 ODF and other industry standards |